Iec 60870-5-103 Interface - Toshiba GRL100-701B Instruction Manual

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

4.5 IEC 60870-5-103 Interface

The GRL100 can support the IEC60870-5-103 communication protocol. This protocol is mainly
used when the relay communicates with a control system and is used to transfer the following
measurand, status data and general command from the relay to the control system.
• Measurand data: current, voltage, active power, reactive power, frequency
• Status data:
The IEC60870-5-103 function in the relay can be customized with the original software
"IEC103 configurator". It runs on a personal computer (PC) connected to the relay, and can help
setting of Time-tagged messages, General command, Metering, etc. For details of the setting
method, refer to "IEC103 configurator" manual. For the default setting of IEC60870-5-103, see
Appendix Q.
The protocol can be used through the RS485 port on the relay rear panel and can be also used
through the optional fibre optical interface.
The relay supports two baud-rates 9.6kbps and 19.2kbps.
The data transfer from the relay can be blocked by the setting.
For the settings, see the Section 4.2.6.4.
4.6 Clock Function
The clock function (Calendar clock) is used for time-tagging for the following purposes:
• Event records
• Disturbance records
• Fault records
• Metering
• Automatic supervision
• Display of the system quantities on the digest screen
• Display of the fault records on the digest screen
• Display of the automatic monitoring results on the digest screen
The calendar clock can run locally or be synchronized with the external IRIG-B time standard
signal, RSM, IEC or GPS clock. This can be selected by setting.
If it is necessary to synchronize with the IRIG-B time standard signal or GPS signal, it is possible
to transform GMT to the local time by setting.
When the relays are connected to the RSM system as shown in Figure 4.4.1, the calendar clock
of each relay is synchronized with the RSM clock. If the RSM clock is synchronized with the
external time standard (GPS clock etc.), then all the relay clocks are synchronized with the
external time standard.
UTP cable
(10Base-T)
PC
Figure 4.4.2 Relay Setting and Monitoring System (2)
events, fault indications, etc.
 233 
Other
relays
HUB.
6 F 2 S 0 8 5 0
214B-13-10
100/110/115/120V
Relay