Hardware Tests - Toshiba GRL100-701B Instruction Manual

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

6.4 Hardware Tests

The tests can be performed without external wiring, but DC power supply and AC voltage and
current source are required.
6.4.1
User Interfaces
This test ensures that the LCD, LEDs and keys function correctly.
LCD display
• Apply the rated DC voltage and check that the LCD is off.
Note: If there is a failure, the LCD displays the "Auto-supervision" screen when the DC voltage is
applied.
• Press the RESET key for 1 second when the LCD is off, and check that black dots appear on
the whole screen.
LED display
• Apply the rated DC voltage and check that the "IN SERVICE" LED is lit in green.
• Press the RESET key for 1 second when the LCD is off, and check that seven LEDs under
the "IN SERVICE" LED and two LEDs for monitoring jacks A and B are lit in red.
VIEW and RESET keys
• Press the VIEW key when the LCD is off and check that the "Metering" screen is displayed
on the LCD.
• Press the RESET key and check that the LCD turns off.
Keypad
• Press any key on the keypad when the LCD is off and check that the LCD displays the
"MENU" screen. Press the END key to turn off the LCD.
• Repeat this for all keys.
 240 
6 F 2 S 0 8 5 0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grl100-702bGrl100-711bGrl100-712b