[Testing of Zone 1 bending characteristic]
The test circuit and test method is same as above.
The operating voltage of Zone 1 bending characteristic can be calculated as follows:
X
0
X
1
1
1
=
⋅
=
V
X
I
p
θ
sin
1
where,
X
is the Z1S setting reach.
1
θ
is the angle difference between voltage and current.
Note: Toshiba recommend that a minimum of three values for θ be tested to check that the
correct relay settings have been applied.
Care must be taken in choosing values of θ to ensure that the testing points come within
the operating boundary defined by the Z1S θ 2 setting and either the load blinder or mho
settings, as appropriate
(X
, R
)
1
1
θ
1
θ
2
θ
tan
+
1
θ
tan
1
2
⋅
⋅
I
θ
θ
tan
sin
+
1
θ
tan
255
θ
: Z1Sθ1 setting angle
1
θ
: Z1Sθ2 setting angle
2
R