2.6 Transfer Trip Function

The GRL100 provides the transfer trip function which receives a trip signal from the remote
terminal and outputs a trip command. Two transfer trip commands are provided. The scheme
logic is shown in Figure 2.6.1. When the scheme switch [TTSW∗] is set to "TRIP", the binary
output for tripping is driven. When set to "BO", the binary output for tripping is not driven and
only user-configurable binary output is driven.
The sending signal is configured by PLC function. If the sending signal is assigned on a per
phase basis by PLC, a single-phase tripping is available.
Transfer Trip Command 1
1688
From
Remote
1689
Terminal 1
1690
1720
From
Remote
1721
Terminal 2
1722
1595
TR1_BLOCK
Transfer Trip Command 2
1692
From
Remote
1693
Terminal 1
1694
1724
From
Remote
1725
Terminal 2
1726
1596
TR2_BLOCK
TR1-A-R1
≥1
TR1-B-R1
≥1
TR1-C-R1
≥1
TR1-A-R2
TR1-B-R2
TR1-C-R2
[TTSW1]
+
1
TR2-A-R1
≥1
TR2-B-R1
≥1
TR2-C-R1
≥1
TR2-A-R2
TR2-B-R2
TR2-C-R2
[TTSW2]
+
1
Figure 2.6.1
 87 
419
&
420
&
421
&
TR1_3PTP
1660
423
&
424
&
425
&
"TRIP
"BO"
427
&
428
&
429
&
TR2_3PTP
1661
431
&
432
&
433
&
"TRIP
"BO"
Transfer Trip Scheme Logic
6 F 2 S 0 8 5 0
TR1-A TP
≥1
TR1-B TP
≥1
TR1-C TP
≥1
TR1 TRIP
418
≥1
&
INTER TRIP1-A
INTER TRIP1-B
INTER TRIP1-C
422
≥1
INTER TRIP1
TR2-A TP
≥1
TR2-B TP
≥1
TR2-C TP
≥1
TR2 TRIP
426
≥1
&
INTER TRIP2-A
INTER TRIP2-B
INTER TRIP2-C
430
≥1
INTER TRIP2