(0.3 - 0.4Ω
0.1 - 1.0Ω
(0.5 - 5.0Ω
1.01 - 10.0Ω
(5.1 - 50.0Ω
10.01 - 20.0Ω
(50.1 - 100Ω
20.01 - 50.0Ω
(100.1 - 250Ω
50.01 - 100Ω
(250.1 - 500Ω
(*) Values shown in parentheses are in the case of 1A rating. Other values are in the case of 5A
rating.
Set the test voltage and test current phase relation as shown below. That is, V a , V b , and V c
are balanced, and IT lags V a by θ or θ + 180°. θ is 90 ° when testing.
V a
V c
Z1G, Z2G, and Z3G
Adjust the magnitude of Va while retaining the conditions above and measure the voltage at
which the element operates.
The theoretical operating voltage Vop is obtained by the following equations when the
setting reach is ZG. Check that the measured voltage is within the above-mentioned error of
the theoretical voltage.
Z1G, Z2G: Vop = ZG × ( IT +
Z3G, Z4G, ZRG: Vop = IT × ZG
Element
ZG
Z1G
Z2G
Z3G
Z4G
ZRG
PSBGIN
PSBGOU
T
4A)
10A
2A)
5A
1A)
2.5A
0.5A)
1A
0.2A)
0.6A
0.12A)
IT
θ
V b
K xs
100
3
IT
 257 
±5%
±5%
±5%
±7%
±10%
V a
IT
V c
Z4G
1
× IT )
Vop
Measured voltage
6 F 2 S 0 8 5 0
θ+180°
V b