TECHNICAL DATA
Ratings
AC current I
:
n
AC voltage
Frequency:
DC power supply:
AC ripple on DC supply IEC60255-11
DC supply interruption IEC60255-11
Permissive duration of DC supply voltage
interruption to maintain normal operation:
Restart time:
Binary input circuit DC voltage:
Overload Ratings
AC current input
AC voltage input
Burden
AC current input
AC voltage input
DC power supply:
Binary input circuit:
Phase-segregated Current Differential Protection
DIFI1 (Small current region)
DIFI2 (Large current region)
Operating time
Resetting time
Zero-sequence Current Differential Protection for high-resistance earth
DIFGI
Timer
Operating time
Resetting time
Charging Current Compensation
DIFIC
Differential Current Supervision
DIFSV
Timer
Out-of-step protection
Out-of-step trip
1A or 5A
100V, 110V, 115V, 120V
50Hz or 60Hz
110Vdc/125Vdc (Operative range: 88 - 150Vdc)
220Vdc/250Vdc (Operative range: 176 - 300Vdc)
48Vdc/54Vdc/60Vdc (Operative range: 38.4 - 72Vdc)
24Vdc/30Vdc (Operative range: 19.2 – 36Vdc)
maximum 12%
up to 50ms at 110V
less than 10s
110/125Vdc
220/250Vdc
48/54/60Vdc
24/30Vdc
4 times rated continuous
100 times rated for 1s
2 times rated continuous
0.2VA per phase (at rated 5A)
0.4 VA at zero-sequence circuit (at rated 5A)
0.1VA per phase (at rated 1A)
0.3 VA at zero-sequence circuit (at rated 1A)
0.1VA (at rated voltage)
less than16W (quiescent)
less than 25W (operation)
≤ 0.5W per input at 110Vdc
0.10 to 2.00A in 0.01A steps (1A relay)
0.50 to 10.00A in 0.01A steps (5A relay)
0.6 to 24.0A in 0.1A steps (1A relay)
3.0 to 120.0A in 0.1A steps (5A relay)
less than 1 cycle at 300% of DIFI1
less than 110ms (for tripping output)
less than 40ms (for signal output)
0.05 to 1.00A in 0.01A steps (1A relay)
0.25 to 5.00A in 0.01A steps (5A relay)
0.00 to 10.00s in 0.01s steps
less than 45ms
less than 100ms
0.00 to 1.00A in 0.01A steps (1A relay)
0.00 to 5.00A in 0.01A steps (5A relay)
0.05 to 2.00A in 0.01A steps (1A relay)
0.25 to 10.00A in 0.01A steps (5A relay)
0 to 60s in 1s steps
OFF / TRIP / BO(separated from other trip signals)