Toshiba GRL100-701B Instruction Manual page 277

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

6 F 2 S 0 8 5 0
The fault locator starts measurement when the current differential protection operates.
Therefore, it is preferable to test it whilst testing the protection schemes by applying a fault.
The line parameter settings must be changed to meet those of the test set.
The measurement result is expressed as a percentage of the line length and the distance, and is
displayed on the "Fault Record" screen of the LCD.
 276 