1. Failed module tracing and its replacement
If the "ALARM" LED is ON, the following procedure is recommended. If not repaired, contact
the vendor.
Procedure
"ALARM" LED ON?
Any LCD messages?
Press [VIEW] key
Locate the failed module.
DC supply "OFF"
Module replacement
DC supply "ON"
"ALARM" LED OFF?
No
No
Yes
Not displayed
No
End
 458 
Countermeasure
No failure
Press [VIEW] key
Yes
Locate the failed module referring to Table S-1.
Caution: Check that the replacement module has an
identical module name (VCT, SPM, IO1,
IO2, etc.) and hardware type-form as the
failed module. Furthermore, the SPM
module must have the same software
name and version. Refer to Section
4.2.5.1.
As shown in the table, some of the messages cannot
identify the fault location definitely but suggest plural
possible failure locations. In these cases, the failure
location is identified by replacing the suggested
failed modules with spare modules one by one until
the "ALARM" LED is turned off.
If both "IN SERVICE" LED and "ALARM" LED are
OFF, check the followings.
Check: Is DC supply voltage available with the correct
polarity and of adequate magnitude, and
connected to the correct terminals?
6 F 2 S 0 8 5 0
Not displayed
Contact the vendor.
Contact the vendor.