I da , I db , I dc , I d0 , remote terminal 1: I a1 , I b1 , I c1 , 3I 01 remote terminal 2: I a2 , I b2 , I c2 , 3I 02 ), 32
binary signals and the dates and times at which recording started. Any binary signal shown in
Appendix B can be assigned by signal setting of disturbance record. The default setting of binary
signal is shown in Appendix H.
The name of binary signal can be set by RSM100. Maximum 22 characters can be set, but LCD
displays up to 11 characters of them. Therefore, it is recommended the maximum characters are
set. The set name can be viewed on the Setting(view) screen.
The LCD display only shows the dates and times of disturbance records stored. Details can be
displayed on the PC. For how to obtain disturbance records on the PC, see the PC software
instruction manual.
The pre-fault recording time is fixed at 0.3s and the post-fault recording time can be set between
0.1 and 3.0s and the default setting is 1.0s.
The number of records stored depends on the post-fault recording time and the relay model. The
typical number of records stored in 50Hz and 60Hz power system is shown in Table 3.4.3.1.
Note: If the recording time setting is changed, the records stored so far are deleted.
Table 3.4.3.1 Post Fault Recording Time and Number of Disturbance Records Stored
Recording time
50Hz
60Hz
Setting
The elements necessary for starting disturbance recording and their setting ranges are shown in
the table below.
Element
Range
Timer
0.1-3.0 s
OCP-S
0.5-250.0 A
(0.1-50.0 A
OCP-G
0.5-250.0 A
(0.1-50.0 A
UVP-S
0-132 V
UVP-G
0-76 V
(*) Current values shown in the parentheses are in the case of 1A rating. Other current values are in
the case of 5A rating.
Starting the disturbance recording by a tripping command or the starter elements listed above is
enabled or disabled by setting the following scheme switches with identical names with the
starter elements except the switch [TRIP].
Element
Range
[TRIP]
ON/OFF
[OCP-S]
ON/OFF
[OCP-G]
ON/OFF
[UVP-S]
ON/OFF
[UVP-G]
ON/OFF
0.1s
0.5s
1.0s
1.5s
36
18
11
8
30
15
9
6
Step
Default
Remarks
0.1 s
1.0 s
Post-fault recording time
0.1 A
10.0 A
Overcurrent detection (phase fault)
0.1 A
2.0 A) (*)
0.1 A
5.0 A
Overcurrent detection (earth fault)
0.1 A
1.0 A) (*)
1 V
88 V
Undervoltage detection (phase fault)
1 V
51 V
Undervoltage detection (earth fault)
Step
Default
ON
ON
ON
ON
ON
 183 
2.0s
2.5s
3.0s
6
5
4
5
4
3
Remarks
Start by tripping command
Start by OCP-S operation
Start by OCP-G operation
Start by UVP-S operation
Start by UVP-G operation
6 F 2 S 0 8 5 0