Cb1_Cont-A; Cb1_Cont-B - Toshiba GRL100-701B Instruction Manual

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

Further, all binary input functions are programmable by PLC (Programmable Logic Controller)
function.
The default setting of the binary input is shown in Table 3.2.1.2.
Module
BI No.
Name
IO#1
BI1
CB1 AUXILIARY CONTACT - A Ph
BI2
CB1 AUXILIARY CONTACT - B Ph
BI3
CB1 AUXILIARY CONTACT - C Ph
BI4
CB2 AUXILIARY CONTACT - A Ph
BI5
CB2 AUXILIARY CONTACT - B Ph
BI6
CB2 AUXILIARY CONTACT - C Ph
BI7
DISCONNECTOR NORMALLY CLOSED 1542
BI8
DISCONNECTOR NORMALLY OPEN
BI9
SIGNAL RECEIVE (R1)
BI10
SIGNAL RECEIVE (R2)
BI11
(*) DC POWER SUPPLY
BI12
TRANSFER TRIP COMMAND 1
BI13
TRANSFER TRIP COMMAND 2
BI14
DEF SIGNAL RECEIVE (R1)
BI15
DEF SIGNAL RECEIVE (R2)
IO#2
BI16
EXTERNAL TRIP - A Ph
BI17
EXTERNAL TRIP - B Ph
BI18
EXTERNAL TRIP - C Ph
IO#3
BI19
CARRIER PROTECTION BLOCK
BI20
EXTERNAL CB CLOSE COMMAND
BI21
INDICATION RESET
BI22
CB1 AUTORECLISNG READY
BI23
CB2 AUTORECLISNG READY
BI24
AUTORECLOSING BLOCK COMMAND
BI25
Spare
BI26
Spare
BI27
Spare
BI28
Spare
IO#4
BI34
Spare
BI35
Spare
BI36
Spare
Note (∗): If the binary input of DC power supply is OFF, the ready signal of relay is OFF and the
message 'Term∗ rdy off' is displayed. See Section 3.3.6.
(+)
(−)
[BISW1]
BI1
BI1
[BISW2]
BI2
BI2
[BISWn]
BIn
BIn
Table 3.2.1.2 Binary Input Signals
Contents
BI1 command
"Norm"
1
"Inv"
BI2 command
"Norm"
1
"Inv"
BIn command
"Norm"
1
"Inv"
1
0V
Figure 3.2.1.1 Logic Level Inversion
 170 
Setting
Signal No. & Signal Name
1536

CB1_CONT-A

1537

CB1_CONT-B

1538
CB1_CONT-C
1539
CB2_CONT-A
1540
CB2_CONT-B
1541
CB2_CONT-C
DS_N/O_CONT
1543
DS_N/C_CONT
1856
CAR.R1-1
1864
CAR.R2-1
1546
DC_SUPPLY
1547
85S1
1548
85S2
1857
CAR.R1-2
1865
CAR.R2-2
1551
EXT_TRIP-A
1556
EXT_CBFIN-A
See the BISW setting
1552
EXT_TRIP-B
in Relay setting sheet
1557
EXT_CBFIN-B
1553
EXT_TRIP-C
1558
EXT_CBFIN-C
1544
CRT_BLOCK
1545
CB_CLOSE
1549
IND.RESET
1571
CB1_READY
1572
CB2_READY
1573
ARC_RESET
Signal No.
PLC logic
6 F 2 S 0 8 5 0
Norm or Inv
Protection
schemes

Hide quick links: