PSBSZ and PSBGZ have same functions and characteristics as shown in Figures 2.3.3.1 and
2.3.3.2, and block tripping of phase and earth fault elements respectively.
593:PSBSOUT-AB
594:PSBSOUT-BC
595:PSBSOUT-CA
PSBSOUT
596:PSBSIN-AB
597:PSBSIN-BC
598:PSBSIN-CA
PSBSIN
EFL
≥1
PSB_BLOCK
1877
587:PSBGOUT-A
588:PSBGOUT-B
589:PSNGOUT-C
PSBGOUT
590:PSBGIN-A
591:PSBGIN-B
592:PSBGIN-C
PSBGIN
PSB_F.RESET
1987
One- and two-phase faults can be protected with the command protection even during a power
swing.
The PSB can be disabled or reset by the PLC signal PSB_BLOCK or PSB_F.RESET.
&
t
0.02 - 0.06s
T2
t
0
&
0.5s
&
t
0.02 - 0.06s
T2
t
0
&
0.5s
Figure 2.3.3.2 Power Swing Detection Logic
74
TPSB
0
S Q
F/F
R
≥1
TPSB
0
S Q
F/F
R
≥1
6 F 2 S 0 8 5 0
765
PSBS_DET
766
PSB_DET
≥1
764
PSBG_DET