• Enter a signal number 270 for Term B to observe a signal PULSE at monitoring jack B, and
then press the ENTER key.
The phase of the test current is adjusted as follows.
• Adjust the reference voltage to be in-phase with the pulse signal PULSE monitoring a CRT
oscilloscope.
• Adjust the test current to be in-phase with the reference voltage to simulate an infeed current
and counter-phase to simulate an outflow current.
PULSE
signal
Reference
voltage
Testing
current
Percentage restraint characteristics
The percentage restraint characteristic is tested on the outflow current (I out ) and infeed current
(I in ) plane as shown in Figure 6.5.1.5 by applying an infeed current to one relay and an outflow
current to another relay.
I out
DIFI2
DIFI1
DIFI1, DIFI2: Setting value
Figure 6.5.1.5 Percentage Restraining Characteristic on I in -I out Plane
Characteristic A is expressed by the following equation,
I out ≤ (5/7) (I in - DIFI1)
Characteristic B is expressed by the following equation,
One cycle (20ms or 16.7ms)
Figure 6.5.1.4 Phase Adjustment
I in = I out
B
A
DIFI1 + 7/5 DIFI2
 251 
6 F 2 S 0 8 5 0
Time