Setting
The table shows the setting elements necessary for the overvoltage protection and their setting
ranges.
Element
Range
OVS1
5.0 – 150.0 V
TOS1I
0.05 – 100.00
TOS1
0.00 – 300.00 s
TOS1R
0.0 – 300.0 s
OS1DP
10 – 98 %
OVS2
5.0 – 150.0 V
TOS2
0.00 – 300.00 s
OS2DP
10 - 98 %
OVG1
5.0 – 150.0 V
TOG1I
0.05 – 100.00
TOG1
0.00 – 300.00 s
TOG1R
0.0 – 300.0 s
OG1DP
10 – 98 %
OVG2
5.0 – 150.0 V
TOG2
0.00 – 300.00 s
OG2DP
10 – 98 %
[OVS1EN]
Off / DT / IDMT
[OVS2EN]
Off / On
[OVG1EN]
Off / DT / IDMT
[OVG2EN]
Off / On
Step
Default
Remarks
0.1 V
120.0 V
OVS1 threshold setting.
0.01
10.00
OVS1 time multiplier setting. Required if [OVS1EN] = IDMT.
0.01 s
0.10 s
OVS1 definite time setting. Required if [OVS1EN] = DT.
0.1 s
0.0 s
OVS1 definite time delayed reset.
1 %
95 %
OVS1 DO/PU ratio setting.
0.1 V
140.0 V
OVS2 threshold setting.
0.01 s
0.10 s
OVS2 definite time setting.
1 %
95 %
OVS2 DO/PU ratio setting.
0.1V
70.0 V
OVG1 threshold setting.
0.01
10.00
OVG1 time multiplier setting. Required if [OVG1EN]=IDMT.
0.01 s
0.10 s
OVG1 definite time setting. Required if [ZOV1EN]=DT.
0.1 s
0.0 s
OVG1 definite time delayed reset.
1 %
95 %
OVG1 DO/PU ratio
0.1V
80.0 V
OVG2 threshold setting
0.01 s
0.10 s
OVG2 definite time setting
1 %
95 %
OVG2 DO/PU ratio
Off
OVS1 Enable
Off
OVS2 Enable
Off
OVG1 Enable
Off
OVG2 Enable