90 ° .
• Check that the A-phase differential current I da on the "Metering" screen coincides with the I d
mentioned above with an error within ± 7%.
End-to-end test setup
When the percentage restraint characteristic is checked, an end-to-end setup using two relays is
required.
<Testing at laboratory>
If the relays can be collected and tested at a laboratory, the end-to-end test is possible by directly
connecting their communication ports. Figure 6.5.1.3 (a) shows the testing circuit of the
laboratory end-to-end test.
In case of two-terminal applications, the signal terminals CH1-TX1 and -RX1 of one relay are
directly connected to CH1-RX1 and -TX1 of another relay.
Note: When the relays have an electrical telecommunications interface in accordance with
CCITT-G703-1.2.1 or an optical interface (Short wavelength light, GI, 2km class), the scheme
switch [D. test] must be set to "1" (= On) to test them under the direct connection of the
communication circuits.
 247 
6 F 2 S 0 8 5 0