6.5.1.3
Distance Measuring Element Z1, Z2, Z3, Z4, ZR and PSB
Phase fault element reach test
The test voltage and current input test circuit is shown in Figure 6.5.1.6.
Three-phase
voltage
source
A
Single-phase
current
source
+
DC
power
supply
DC
voltmeter
Phase fault elements and their output signal numbers are listed below.
Measuring element
Z1S-AB
Z2S-AB
Z3S-AB
Z4S-AB
ZRS-AB
PSBSIN-AB
PSBSOUT-AB
• Press 5 (=Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
• Enter a signal number to be observed at monitoring jack A and press the ENTER key.
• Apply three-phase rated voltage.
Choose a test current IT by referring to the table below, the table shows the relationship
between the reach setting, test current and measuring error.
V
V
φ
φ
Figure 6.5.1.6 Testing Phase-Fault Element
Signal number
575
578
581
584
364
596
593
 253 
GRL100
V
TB1
-11
V a
-12
V b
-13
V c
-14
Monitoring
φ
jack
TB1
-1
I a
-2
-3
I b
-4
TB4
-A16
-A17
E
6 F 2 S 0 8 5 0
A
0V