ABB i-bus KNX Product Manual page 108

Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Start-up
No.
38
The device sends information to this communication on whether automatic control has been activated or deactivated.
Telegram value:
39
The device uses this communication object to send the status information to each output.
The Low Byte (Bit no. 0...7) contains the information on the current operating state. Only one status can ever be active.
The High Byte (Bit no. 8...15) is not assigned in the operation mode Ventilation flaps, switch mode.
The current status or communication object value is sent after a change or request by the communication object Request
status values.
For further information, see:
information (Bit
Low Byte
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:
High Byte
Bit 8:
Bit 9:
Bit 10:
Bit 11:
Bit 12:
Bit 13...15
106 2CDC 506 051 D0204 | JRA/S
Function
Status Automatic
0 = Automatic control deactivated
1 = Automatic control activated
Status information
Code table Scene (8 bit), DPT
0...7), p. 123 in the appendix
Manual operation
Telegram value 0: Inactive
Telegram value 1: Active
Block active
Telegram value 0: Inactive
Telegram value 1: Active
Forced operation
Telegram value 0: Inactive
Telegram value 1: Active
Frost alarm
Telegram value 0: Inactive
Telegram value 1: Active
Rain alarm
Telegram value 0: Inactive
Telegram value 1: Active
Wind alarm
Telegram value 0: Inactive
Telegram value 1: Active
Automatic sun protection
Telegram value 0: Inactive
Telegram value 1: Active
Automatic heating/cooling
Telegram value 0: Inactive
Telegram value 1: Active
Drive error (no current detection on activated drive, only for devices of type JRA/S x.y.5.1)
Telegram value 0: No error
Telegram value 1: Error
Drive in motion or relays activate drive
Telegram value 0: No
Telegram value 1: Yes
Drive turns to CLOSED or relays control drive in the CLOSED direction
Telegram value 0: No
Telegram value 1: Yes
Drive turns to OPEN or relays control drive in the OPEN direction
Telegram value 0: No
Telegram value 1: Yes
Send and receive delay active
Telegram value 0: No
Telegram value 1: Yes
Not assigned
Object name
Output A
Output A
18.001, p. 122 and
Code table for communication object Status
Data type
Flags
1 bit
C, R, T
DPT 1.002
2-byte
C, R, T
Non DPT

Advertisement

Table of Contents
loading

Table of Contents