ABB i-bus
KNX
Start-up
Order of priority for safety alarm
functions
Options:
This parameter determines the sequence of priorities for the safety functions Weather alarms (wind, rain,
frost), Block and Forced operation. These functions have a higher priority than all other functions. If one of
these functions is activated, the operation of the blind/shutter is disabled. This also applies during manual
operation.
A priority must also be defined for safety functions among one another. In this way, the blind/shutter is
correctly controlled if more than one security function is activated simultaneously. Forced operation, for
example, has priority over a wind alarm when cleaning the windows, so that the cleaning personnel are not
hindered by an UP telegram resulting from a wind alarm.
Note
Wind, rain and frost alarms are only activated if in parameter window Weather alarms, the
communication objects are enabled and linked to the group addresses!
1. Weather alarm – 2. Block – 3. Forced operation
1. Weather alarm - 2. Forced operation - 3. Block
1. Block - 2. Weather alarm - 3. Forced operation
1. Block - 2. Forced operation - 3. Weather alarm
1. Forced operation - 2. Block - 3. Weather alarm
1. Forced operation - 2. Weather alarm - 3. Block
JRA/S | 2CDC 506 051 D0204 57