ABB i-bus KNX Product Manual page 110

Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Start-up
No.
37
The output sends information to this communication object if the output operation is enabled or blocked. Operation is blocked
is either one of the safety functions has been activated, e.g. wind alarm, or if the device is in manual operation.
Telegram value:
39
The device uses this communication object to send the status information to each output.
The Low Byte (Bit no. 0...7) contains the information on the current operating state.
High Byte (Bit no. 8...15) contains additional information, specially for the connected drive.
The current status or communication object value is sent after a change or request by the communication object Request
status values.
For further information, see:
information (Bit
Low Byte
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:
High Byte
Bit 8...15:
108 2CDC 506 051 D0204 | JRA/S
Function
Status Operability
Example
An LED on the push button can display to the user that the operation of the blind/shutter is not possible via
push buttons.
0 = Operation enabled
1 = Operation disabled
Status information
Code table Scene (8 bit), DPT
0...7), p. 123 in the appendix.
Manual operation
Telegram value 0: Inactive
Telegram value 1: Active
Block active
Telegram value 0: Inactive
Telegram value 1: Active
Forced operation
Telegram value 0: Inactive
Telegram value 1: Active
Frost alarm
Telegram value 0: Inactive
Telegram value 1: Active
Rain alarm
Telegram value 0: Inactive
Telegram value 1: Active
Wind alarm
Telegram value 0: Inactive
Telegram value 1: Active
Not used
Not used
Not used
Object name
Output A
Output A
18.001, p. 122 and
Code table for communication object Status
Data type
Flags
1 bit
C, R, T
DPT 1.002
2-byte
C, R, T
Non DPT