Parameter window General

The higher-level parameters can be set in this parameter window.
Time-delayed switching of drives
Options:
In larger KNX systems, a high starting current peak is generated if all drives start simultaneously due to
central telegrams. The starting current peak can be limited by a time delayed switching of the outputs. The
central travel telegrams are executed with a delay. The time delay when implementing a travel movement
applies for the following communication objects or states (even for activated automatic control):
Move to height for sun [0...255], Adjust slat for sun [0...255] Block, Forced operation
Wind alarm, Rain alarm, Frost alarm
Move to height position [0...255]
Move slats [0...255]
Programming, Reset
Bus voltage failure
Bus voltage recovery
Position on reset of weather alarm, blocking and forced operation
The time delay when undertaking a movement action is not considered for the following communication
objects:
Move blinds/shutter up-down, blinds/shutter up-down limited
Slat adjustment/stop up/down, stop
Move to position 1, 2, Move to position 3, 4
This ensures that the direct operation function, e.g. via a push button, is not time delayed.
Activated: The parameter Time delay in s appears.
40 2CDC 506 051 D0204 | JRA/S
Deactivated
Activated