ABB i-bus
KNX
Start-up
No reaction: Any movement currently being undertaken is completed.
Up or Down: The blind/shutter moves up or down.
Stop: Any movement currently being undertaken by the blind/shutter is stopped immediately. The
outputs are disconnected from the voltage supply.
Position 1-4: If one of these positions are selected, the blind/shutter moves to a preset position. The
blind/shutter height and slat setting of the corresponding position can be set in parameter window A:
Positions/Presets, p. 72.
Individual position: A freely-definable position is set on Sun = 1 or 0. The following parameters appear:
Receive position and slat via object: This option is suitable particularly in conjunction with the Shutter
Control Unit JSB/S.
Note
This parameter is available exclusively in the operation mode Control with slat adjustment.
Receive only slat via object: With activated automatic function and Sun = 1, only the value on the
communication object Adjust slat for sun [0...255] is evaluated.
Note
This parameter is available exclusively in the operation mode Control with slat adjustment.
Note
A slat adjustment is not carried out if the blind/shutter is in its upper end position.
Receive position via object: The position of the blind/shutter is received via the communication object
Adjust slat for sun [0...255].
Note
This parameter is available exclusively in the operation mode Control without slat adjustment.
Position height in %
(0% = top; 100% = bottom)
Position Slat in % [0...100]
(0% = open; 100% = closed)
Note
The parameters for slat adjustment are available exclusively in the operation mode Control with
slat adjustment.
These parameters specify the height or the slat position of the blind/shutter.
Options:
0...100
JRA/S | 2CDC 506 051 D0204 77