KNX
Start-up
Order of priority for safety alarm
functions
Options:
This parameter determines the sequence of priorities for the safety functions Weather alarms (wind, rain,
frost), Block and Forced operation. These functions have a higher priority than all other functions. If one of
these functions is activated, the operation of the output is disabled. This also applies during manual
operation.
A priority must also be defined for safety functions among one another. In this way, the output is correctly
controlled if more than one security function is activated simultaneously.
Note
Wind, rain and frost alarm are only activated if, on the page Weather alarms, the communication objects
are enabled and linked to the group addresses!
92 2CDC 506 051 D0204 | JRA/S
1. Weather alarm - 2. Block - 3. Forced operation
1. Weather alarm - 2. Forced operation - 3. Block
1. Block - 2. Weather alarm - 3. Forced operation
1. Block - 2. Forced operation - 3. Weather alarm
1. Forced operation - 2. Block - 3. Weather alarm
1. Forced operation - 2. Weather alarm - 3. Block