Communication Objects, Output A - ABB i-bus KNX Product Manual

Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Start-up
Communication objects, output A...X Control with and without slat adjustment
3.3.3
These communication objects are available to each output and are used for channel-specific functions.
The following section describes the communication objects for the operation modes Control with slat
adjustment and Control without slat adjustment.
No.
10
If a telegram with the value 0 is received at this communication object, the blind/shutter is moved upwards to the rest position
or to the upper end position. If a telegram with the value 1 is received, the blind/shutter is moved downwards.
Telegram value
11
When a telegram is received (irrespective of whether the value is 0 or 1) at this communication object, the movement is
stopped.
1
Operation mode Control with slat adjustment: When the blind/shutter is at rest and a telegram is received at this
communication object, a slat adjustment upwards (0 = OPEN) or downwards (1 = CLOSE) is carried out.
2
Operation mode Control without slat adjustment: When the blind/shutter is at rest and a telegram is received, no action is
undertaken.
Telegram value
12
This communication object is enabled if in the parameter window Blinds/shutter, page 63, the option Via object
"Blinds/shutter up-down limited" was selected under the parameter Limit traveling range. If a telegram with the value 0 is
received at this communication object, the blind/shutter will move upwards to the parameterized limit. If a telegram with the
value 1 is received, the blind/shutter will move downwards to the parameterized limit. The blind/shutter is stopped
automatically if the parameterized upper or lower limit is reached.
Telegram value
12
This communication object is enabled if, in the parameter window Blinds/shutter, page 63, the option Via object "Enable
limitation" was selected under the parameter Limit travelling range. The parameters can be used to set whether the limitation
should be executed for a direct telegram or an automatic telegram.
Telegram value:
Function
Move blinds/shutter up-down
0 = UP
1 = DOWN
1
Slat adjustm./stop up-down
2
Stop Up-Down
0 = STOP/open slat adjustment
1 = STOP/slat adjustment close
Blinds/shutter up-down limited
0 = Limited UP
1 = Limited DOWN
Enable limitation
0 = Limitation inactive
1 = Limitation active
Object name
Output
Output A
Output A
Output A
Data type
Flags
1 bit
C, W
DPT 1.008
1 bit
C, W
DPT 1.007
1 bit
C, W
DPT 1.008
1 bit
C, W
DPT 1.003
JRA/S | 2CDC 506 051 D0204 99

Advertisement

Table of Contents
loading