Parameter window A: Blinds/shutter

In this parameter window, specific settings for the blind/shutter to be controlled are undertaken.
Note
All the functions and parameters, which relate to settings for slats in the following section, are only
available in the operation mode Control with slat adjustment.
Determine times for slat
Options:
Via duration of slat adjustment (step): The following parameters appear:
Via duration of slat adjustment (step)
Via total duration for slat turning
Duration of slat adjustment
(step) in ms [50...1,000]
50...200...1,000 ms
Options:
This parameter specifies the time during which the slats of the blind/shutter, e.g. blind, open or
close in each slat adjustment.
Number of slat adjustments
(from 0% = open to 100% = closed)
1...7...60
Options:
This parameter defines the number of slat adjustments (steps) which are required to tilt the slats
from fully closed to fully open. The appropriate adjustment angle for each slat adjustment is
calculated from the duration, slat adjustment and the number of the slat adjustments.