KNX
Commissioning
3.2.1

Parameter window General

Higher level parameters can be set in the parameter window General.
Sending and switching delay after
bus voltage recovery in s [2...255]
Options:
Telegrams are only received during the send and switching delay. The telegrams are not processed how-
ever, and the outputs remain unchanged. No telegrams are sent on the bus.
After the sending and switching delay, telegrams are sent, and the state of the outputs is set to correspond
to the parameterization or the communication object values.
If communication objects are read during the sending and switching delay, e.g. by a visualisation system,
these read requests are stored, and a response is sent, after the send and switching delay has been com-
pleted.
An initialisation time of about two seconds is included in the delay time. The initialisation time is the time
that the processor requires to be ready to function.
2...255
How does the device behave with bus voltage recovery?
After bus voltage recovery, the device always waits for the send delay time to elapse before send-
ing telegrams on the bus.
SE/S 3.16.1 | 2CDC 505 084 D0203 29