ABB i-bus KNX Product Manual page 140

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Planning and application
Switch (Output A...C)
Behaviour with:
Communication object:
Switch
Communication object:
Disable function time
138 2CDC 505 084 D0203 | SE/S 3.16.1
Bus voltage recovery
Download
Programmable (Parameter
Unchanged. Evaluation
window X: General), the
only after a new event has
state that the output should
been received.
assume at bus voltage
Remark: Any manual
failure.
switching that may have
The value with which the
occurred will be reset.
CO Switch should be
written after bus voltage
recovery can also be
parameterized.
write with 1:
The processing chain for
the value 1 restarts.
write with 0:
The processing chain for
the value 0 restarts.
not write:
The value before bus
voltage failure is restored.
The processing chain
restarts.
Note: Before the very first
download (device fresh
from the factory), the value
before bus voltage failure
is not defined. For this
reason, the communication
object is written with 0 and
the contact is opened.
If opening of the contact at
bus voltage recovery
before the first download
(building phase) is not
desired, this can be
prevented by temporary
removal of the KNX
voltage.
In Parameter window
Unchanged.
X: Function, you can set if
Timers are out of opera-
the function Time is
tion.
disabled or not disabled
after bus voltage recovery.
Timers are out of opera-
tion.
ETS reset
Full download / applica-
tion update
Programmable (Parameter
Programmable (Parameter
window X: General), the
window X: General), when
state that the output should
the setting unchanged is
assume at bus voltage
set, the state 0 is set.
failure.
The value with which the
CO Switch should be
written after bus voltage
recovery can also be
parameterized.
write with 1:
The processing chain for
the value 1 restarts.
write with 0:
The processing chain for
the value 0 restarts.
not write:
The value before bus
voltage failure is restored.
The processing chain
restarts.
As with bus voltage
As with bus voltage
recovery
recovery