ABB i-bus KNX Product Manual page 137

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Planning and application
Reaction at bus voltage recovery and ETS reset
With the following communication objects, you can parameterize the value at which they should be written
after bus voltage recovery or an ETS reset:
Switch
Disable function time
Logical connection 1/2
Forced operation
Load control deactivation master (only the value of the communication object at bus voltage recovery
can be parameterized)
Load control deactivation slave (only the value of the communication object at bus voltage recovery
can be parameterized)
What is an ETS reset?
Generally an ETS reset is defined as a reset of the device via the ETS. The ETS reset is initiated in the
ETS3 under the menu point Commissioning with the function Reset device. This stops the user program
and it is restarted.
What is the difference between a download and a full download or an application update?
In the ETS, a differentiation can normally be made between partial programming and a download of the
complete application program. ABB i-bus
selection Application program under the menu item Commissioning > Download. A download of the com-
plete application program, provided that only the parameter settings are changed, is unnecessary and
takes time.
Note
The download column in the following table applies both for partial download as well as the download of
the complete application. If the device is discharged via the ETS (Commissioning > Unload...) or if a
new version of the application is loaded, the behaviour at full download/application update (right column
applies).
In the following table, the behaviour of the Energy Actuator is represented in the overview:
®
devices generally only perform a partial download even with the
SE/S 3.16.1 | 2CDC 505 084 D0203 135