Device Technology; Energy Actuator Se/S 3.16.1, Mdrc; Technical Data - ABB i-bus KNX Product Manual

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX

Device technology

2
Device technology
2.1

Energy Actuator SE/S 3.16.1, MDRC

SE/S 3.16.1
2.1.1

Technical data

Supply
Rated output value
Switching current
Relay service life
Measuring range
The Energy Actuator is a modular
installation device in Pro M design for
installation in the distribution board. The
device is especially suitable for switching
loads with high peak inrush currents
such as lighting equipment with compen-
sation capacitors or fluorescent lamp
loads (AX) to EN 60 669.
Manual operation is possible using a
keypad on the device. This simultane-
ously indicates the switching state.
The Energy Actuator can switch up to
3 independent electrical loads via float-
ing contacts. The maximum load current
per output is 20 A.
Bus voltage
Current consumption via bus
Power consumption via bus
Power consumption on mains
Number of switch outputs (floating)
U
rated voltage
n
I
rated current
n
Leakage loss per device at max. load 3 x 16 A
Leakage loss per device at max. load 3 x 20 A
operation (cos ϕ = 0.45)
2)
AC3
to EN 60 947-4-1
operation (cos ϕ = 0.8)
2)
AC1
to EN 60 947-4-1
C-Load switching capacity
Fluorescent lighting load to EN 60 669-1
Minimum switching power
DC current switching capacity (resistive load)
Mechanical service life
Electrical endurance
to IEC 60 947-4-1
(240 V/cos ϕ = 0.8)
1)
AC1
(240 V/cos ϕ = 0.45)
1)
AC3
(240 V/cos ϕ = 0.45)
1)
AC5a
Active consumption/active power
Current (AC)
Voltage (AC)
Frequency
The connection of the outputs is imple-
mented using universal head screw
terminals. Each output is controlled
separately via the KNX.
Individual outputs can be copied or
exchanged to reduce the programming
effort.
The parameterization is undertaken via
the ETS. The connection to the KNX is
implemented using the bus connection
terminal on the front.
21...30 V DC
< 12 mA
Maximum 250 mW
≤ 0.7 W
3
250/440 V AC (50/60 Hz)
16/20 AX, C-Load
3.0 W
4.2 W
16 A/230 V AC
16/20 A/230 V AC
20 A
16/20 AX/250 V AC (200 µF)
2)
100 mA/12 V AC
100 mA/24 V AC
20 A/24 V DC
6
> 10
switching operations
5
> 10
switching operations
4
> 3 x 10
switching operations
4
> 3 x 10
switching operations
5.7 W...4,600 W (U
= 230 V)
n
2.8 W...2,300 W (U
= 115 V)
n
0.025...20 A
95...265 V
45...65 Hz
SE/S 3.16.1 | 2CDC 505 084 D0203 7