ABB i-bus KNX Product Manual page 111

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
No.
63
This communication object is enabled if in parameter window
been selected with the option yes.
With this communication object, the output can be forcibly switched on.
If the communication object is assigned with the value 1, the output is switched on irrespective of the value of the object
Switch and remains switched on until the communication object Permanent ON has the value 0. After ending the permanent
ON state, the state of the communication object Switch is used.
Permanent ON only switches ON and "masks" the other functions. This means that the other functions (e.g. staircase)
continue to run in the background but do not initiate a switching action. After the end of Permanent ON, the switching state,
which would result without the Permanent ON function, becomes active. The behaviour for the function staircase lighting after
permanent ON is programmed in parameter window
This communication object can be used for example to allow the service or maintenance and cleaning personnel to initiate a
permanent ON. The device receives a switch telegram via the switch object.
After a download or bus voltage recovery. Permanent ON becomes inactive.
Telegram value
64
This communication object is enabled if in parameter window
been selected with the option yes.
After bus voltage recovery, in the parameter window A: Function the communication object value with the parameter Value
object "Disable function time" on bus voltage recovery can be determined.
With the blocked function Time, the output can only be switched on or off, the functions Staircase lighting, , ON/OFF delay and
Flashing are not triggered.
Telegram value 1 = disable function time
The contact position at the time of disabling and enabling is retained and will only be changed with the next switch telegram to
the communication object Switch.
65
This communication object is enabled if in parameter window
duration has been selected with the option yes.
The Staircase lighting duration is set here. The time is defined in seconds.
66
This communication object is enabled if in parameter window
selected, and in parameter Warning before end of staircase lighting the option via object or via object and via quick switching
OFF/ON has been selected.
Function
Permanent ON
1 = activates permanent ON mode
0 = deactivates permanent ON mode
Disable function time
0 = Function time enabled
Staircase lighting duration
Staircase lighting warning
Object name
A: Time
A:
Function, page 55, the parameter enable function time has
A:
Time, page 58.
A: Time
A:
Function, page 55, the parameter enable function time has
A: Staircase lighting
A:
Time, page 58, the parameter Change Staircase lighting
A: Staircase lighting
A:
Time, page 58, the function Staircase lighting has been
Data type
Flags
1 bit
C, W
DPT 1.001
1 bit
C, R, W, T
DPT 1.003
2 byte
C, R, W
DPT 7.005
1 bit
C, T
DPT 1.005
SE/S 3.16.1 | 2CDC 505 084 D0203 109