Communication Objects Load Control Master - ABB i-bus KNX Product Manual

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.3.3

Communication objects Load control master

No.
13
This communication object is enabled when in parameter window Function, page 35, the parameter Device is load control
master has been selected with the option yes.
Using this communication object, the function Load control master can be deactivated via the receipt of a corresponding
telegram.
Telegram value:
The value of the communication object after bus voltage recovery can be parameterized in the parameter window
master, page 46.
14
Not assigned.
100 2CDC 505 084 D0203 | SE/S 3.16.1
Function
Deactivate load control
0 = The function Load control master is active.
1 = The function Load control master is deactivated. The communication object Send load shedding
stage is sent with the value "Shedding stage 0", all slaves are thus enabled. The communication object
no. 28 Send load shedding stage is written with the value 128 and sent (shedding stage 0, load control
not active).
Object name
Load control master
Data type
Flags
1 bit
C, R, W
DPT 1.003
Load control