ABB i-bus
KNX
Device technology
2.1.3

Circuit diagram

1 Label carrier
2 Button Programming
3 LED Programming
4 Bus terminal connection
5 Switch position display and ON/OFF actuation
6 Load circuits (A...C) each with 2 screw terminals, neutral conductor (N)
Important
Mains voltage must be present on at least one output, and the neutral conductor must be connected for
supplying power to the measurement section.
No load currents may be conducted via the N terminal on the device. The switched load must be con-
nected directly to the N rail.
Terminals 7 or 8 should be connected directly to the N busbar.
The second N terminal can be used to loop to further Energy Actuators.