ABB i-bus KNX Product Manual page 56

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
Value object "Switch" on
bus voltage recovery and ETS reset
Options:
With this parameter, the output can be influenced after bus value recovery.
not write: After bus voltage recovery, the valid value active before the bus voltage failure is restored.
Note
write with 0: The communication object Switch is written with a 0 at bus voltage recovery. The contact
position is redefined and reset in dependence on the set device parameterization.
write with 1: The communication object Switch is written with a 1 at bus voltage recovery. The contact
position is redefined and reset in dependence on the set device parameterization.
Enable objects "Request status values"
on "General"
<−−− NOTE
54 2CDC 505 084 D0203 | SE/S 3.16.1
not write
write with 0
write with 1
Before the very first download (device fresh from the factory), the value before bus voltage failure is
not defined. For this reason, the communication object is written with 0 and the contact is opened.
If opening of the contact at bus voltage recovery before the first download (building phase) is not
desired, this can be prevented by temporary removal of the KNX voltage.
If the output has been switched manually (on the operating element) or by the receipt of a telegram
on the communication object Scene, this setting will not be taken into consideration after bus volt-
age recovery. Consequently, the switching process after bus voltage recovery is possible irrespec-
tive of the setting not write.

Advertisement

Table of Contents
loading

Table of Contents