ABB i-bus KNX Product Manual page 67

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
Number of flashes: [1...100]
Options:
This parameter defines the maximum number of pulses. This is useful to avoid unnecessary wear of the
contacts caused by flashing.
Contact position after flashing
Options:
This parameter defines the state that the parameter should assume after flashing.
ON: The output is switched on after flashing.
OFF: The output is switched off after flashing.
calculate present contact position: The output assumes the switching state, which it had before flash-
ing commenced.
For further information see:
Note: Consider contact life span and
switching cycles per minute
For further information see:
Note
Only a certain number of switching actions are possible per minute and Energy Actuator. With frequent
switching, a switching delay can occur, as only a certain number of switching actions are possible per
minute, see
1...5...100
ON
OFF
calculate present contact position
Function
chart, page 120
Technical
data, page 7
Technical
data, from page 7. The same applies directly after bus voltage recovery.
SE/S 3.16.1 | 2CDC 505 084 D0203 65