ABB i-bus
KNX
Commissioning
3.2.5

Parameter window A: Function

In this parameter window, the behaviour of the output is determined and different functions can be ena-
bled, where further parameter windows become available.
Enable function time: Delay,
staircase lighting, flashing
Options:
no: The parameter window A: Time for output A is not enabled.
yes: The parameter window A: Time for output A as well as the communication object Disable function
time is enabled. Using this communication object, the function Time can be enabled (telegram with
value 0) or disabled (telegram with value 1) via the bus.
As long as the function Time is disabled, the output can only be switched on and off without delay via the
communication object Switch. The priorities as listed in the
Note
The function Time is only disabled when the ongoing function Time has ended.
During disabling of the output, the higher switching priorities, e.g. the functions Safety, are undertaken.
After the function Time has been enabled, the communication object Permanent ON is enabled. The
output is switched ON via this communication object. It remains switched ON until a telegram with the
value 0 is received by the communication object Permanent ON.
The functions continue to operate in the background during the Permanent ON phase. The contact
position at the end of the Permanent ON phase results from the functions operating in the background.
no
yes
Function
chart, page 120, still remain valid.
SE/S 3.16.1 | 2CDC 505 084 D0203 55