Commissioning
No.
29
This communication object is enabled when in parameter window
be changed has been selected with the option yes, 4 values selectable.
With this communication object, one of the 4 parameterized load limits can be selected as the active load limit.
Value range [0...255]
Telegram value:
The active load limit after download or ETS reset is parameterized.
30
This communication object is enabled when in parameter window
be changed has been selected with the option yes, 4 values selectable.
Four parameterized load limits are available. The active load limit can be viewed using this communication object.
30
This communication object is enabled when in parameter window
be changed has been selected with the option yes, object writable.
Only 1 load limit is available. It can be displayed and modified using this communication object.
Function
Choose load limit
0 = Load limit 1 active
1 = Load limit 2 active
3 = Load limit 3 active
4 = Load limit 4 active
5...255: not allowed.
Send load limit
Receive / send load limit
Object name
Load control master
Load control
master, page 46, the parameter Load limit can
Load control master
Load control
master, page 46, the parameter Load limit can
Load control master
Load control
master, page 46, the parameter Load limit can
Data type
Flags
1 byte
C, W
DPT 5.010
4 byte
C, R, T
DPT 14.056
4 byte
C, R, T
DPT 14.056
SE/S 3.16.1 | 2CDC 505 084 D0203 103