ABB i-bus
KNX
Commissioning
Source for power value 1
Options:
•
none: Power value 1 is not used, the communication object Receive power value 1 is not enabled.
•
active power Output A: The active power of output A is used as power value 1. The communication
object Receive power value 1 is not enabled; it is linked internally.
•
external via object: The communication object Receive power value 1 is enabled and can receive an
external power value via the bus.
Source for power value 2
Options:
The settings and functions are identical to those of the parameter Source for power value 1.
Source for power value 3
Options:
The settings and functions are identical to those of the parameter Source for power value 1.
Source for power value 4
Options:
The settings and functions are identical to those of the parameter Source for power value 1.
Number of additional power values
[0...6]
Options:
Depending on the selection, the communication objects Receive power value 5 to Receive power value 10
are enabled.
48 2CDC 505 084 D0203 | SE/S 3.16.1
none
active power Output A
external via object
none
active power Output B
external via object
none
active power Output C
external via object
none
active power total
external via object
0...6