Commissioning
Enable object "Power factor"
Options:
•
yes: The value of the communication object Power factor (A: Power factor) is enabled. The following
parameters appear:
78 2CDC 505 084 D0203 | SE/S 3.16.1
Send "Apparent power" when
+/- VA [1...4,600]
Options:
1...5...4,600
This parameter determines which changes of the value of the communication object Appar-
ent power are sent.
Send "Apparent power" on request
Options:
no
yes
•
yes: The value of the communication object Apparent power is sent when a telegram is re-
ceived on the communication object Request power values. This communication object is ena-
bled in the parameter window General, page 29 .
Send "Apparent power" cyclically
Options:
no
yes
•
yes: The value of the communication object Apparent power is sent cyclically. The setting of
the cycle time is undertaken in parameter window General, page 29 (parameter Cycle time for
power values).
no
yes
Send "Power factor" after a change
Options:
no
yes
•
yes: The value of the communication object Power factor (A: Power factor) is sent in the event
of a change. The following parameter appears:
Send "Power factor" when
+/- 0.01 x value [1...100]
Options:
1...5...100
This parameter determines which changes of the value of the communication object Power
factor are sent.
Send "Power factor" on request
Options:
no
yes
•
yes: The value of the communication object Power factor is sent when a telegram is received
on the communication object Request instrument values. This communication object is enabled
in the parameter window General, page 29 .