ABB i-bus
KNX
Commissioning
3.3.8.3

Communication objects A: Load control slave

No.
80
This communication object is enabled if in parameter window
has been selected with the option yes.
The output (slave) can be enabled using this communication object. The received shedding stage is not considered and the
internal switching state is established.
Telegram value:
The value of the communication object after bus voltage recovery can be parameterized (parameter window Load control
master).
81
This communication object is enabled if in parameter window
slave has been selected with the option yes.
Using this communication object, the shedding stage of the output (slave) can be read.
If in parameter window A: Load control slave the parameter Load shedding stage can be changed via object has been
selected with the option yes, the shedding stage can also be modified via the bus.
Value range [0...255]
Telegram value:
114 2CDC 505 084 D0203 | SE/S 3.16.1
Function
Deactivate load control
0 = the output (slave) "listens in" on the received shedding stage (communication object 10)
1 = the output (slave) is enabled, the function Load control slave is deactivated
Load shedding stage output
0
= slave is enabled
1...8 = shedding stages [1...8]
9...255
Note
If the slave is assigned (or parameterized) with shedding stage 1...8 and the Energy Actuator receives a
shedding stage via the communication object Receive load shedding stage (no. 10) that is greater than or
equal to the assigned stage, the output switches off. If a shedding stage that is less than the assigned stage
is received, the internal switching state is restored, i.e., if the master sends shedding stage 0, all slaves are
enabled.
If the slave is assigned with shedding stage 0 via communication object no. 81, all shedding stages that are
received via communication object 10 are ignored. The slave is always enabled. If the slave is switched off
by the load control during assignment of shedding stage 0, the internal switching stage is restored.
Object name
A: Load control slave
A:
Function, page 55, the parameter Enable function load control
A: Load control slave
A:
Function, page 55, the parameter Enable function load control
= not allowed.
Data type
Flags
1 bit
C, R, W
DPT 1.003
1 byte
C, R, W, T
DPT 5.010