3.2.4

Parameter window A: General

In parameter window A: General, all the general settings are undertaken for output A.
Note
The Energy Actuator has 3 outputs. However, as the functions for all outputs are identical, only the
functions of output A will be described.
Status response of contact position
Options:
no: The switch state is not actively sent on the bus.
yes: object "Status Switch" An additional Status switch communication object is enabled. Using it, a 1
bit telegram with the actual switch status is sent on the bus. The following parameters appear:
no
yes, object "Status Switch"
Send
Options:
no, update only
after a change
on request
after a change or on request
no, update only: If the status of the switching state changes, this is updated but not sent on the
bus.
after a change: Should the status of the switching state change, this is sent by a telegram via
the communication object.
after request: The status of the switching state can only be sent via the KNX if a telegram with
the parameterized value is received on the communication object Request status values.
after a change or on request: The status of the switching state is only sent via the KNX if the
status changes or a telegram with the parameterized value is received on the communication
object Request status values.