Communication Objects Output A: Switch - ABB i-bus KNX Product Manual

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.3.8

Communication objects Output A: Switch

Note
As the functions are identical for all outputs, they will only be explained for output A.
The descriptions of the parameterization options for Outputs A...X are described from parameter window
A:
General, page 51.
No.
60
This communication object is used for switching of the output ON/OFF. The device receives a switch telegram via the switch
object.
Telegram value
61
This communication object is enabled if in parameter window A: General, page 51, the parameter Status response of contact
position the option yes, object "Status Switch" has been selected.
The communication object value directly indicates the current contact position of the switching relay.
The status value can be inverted.
Telegram value
62
This is a diagnostics byte for the output. The value of the communication object is sent when a telegram is received on the
communication object Request status values.
Telegram value:
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Bit 6...7:
108 2CDC 505 084 D0203 | SE/S 3.16.1
Function
Switch
1 = switch ON
0 = switch OFF
Note
With logical connections or forced operations, a modification of the Switch communication object does not
necessarily lead to a change of the contact position.
For further information see:
Function
Status switch
1 = contact closed or opened (depending on the parameterization)
0 = contact closed or opened (depending on the parameterization)
Status byte
1 = Safety priority 1 active
0 = Safety priority 1 not active
1 = Safety priority 2 active
0 = Safety priority 2 not active
1 = Safety priority 3 active
0 = Safety priority 3 not active
1 = Forced operation active
0 = Forced operation not active
1 = function Time active (staircase lighting, flashing, delay)
0 = function Time not active (staircase lighting, flashing, delay)
1 = active power negative, (i.e., power is fed into the system. An Energy Actuator is not intended for this
application.)
0 = active power positive
Not assigned, 0.
Object name
A: Switch
diagram, page 120
A: Switch
A: Diagnostics
Data type
Flags
1 bit
C, W
DPT 1.001
1 bit
C, W
DPT 1.001
1 byte
C, R, T
non DPT