ABB i-bus KNX Product Manual page 74

Energy actuator se/s 3.16.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
Contact position if safety priority 2
Contact position if safety priority 3
The same programming options exist as those for parameter Contact position if safety priority 1.
Contact position when forced operation
and all safety priority x end
Options:
This parameter is only visible if the forced operation or a function Safety priority x (x = 1, 2 or 3) is activat-
ed.
The contact position of the relay at the end of the forced operation is defined here.
calculate present contact position: After forced operation has ended, the switch value is recalculated
and immediately initiated, i.e., the Energy Actuator output continues to operate normally in the back-
ground during forced operation, the output is not changed and only set after the end of safety priori-
ties.
unchanged: The contact position is retained during forced operation or safety priority. The contact po-
sition only changes when a new switch value is calculated.
72 2CDC 505 084 D0203 | SE/S 3.16.1
Object "Forced operation" on
bus voltage recovery and ETS reset
This parameter is only visible if forced operation is activated.
Depending on whether the Forced operation communication object is a 1 bit or 2 bit communication
object, there are two different parameterization possibilities available:
With selection 1 bit object:
Options:
inactive
active
inactive: Forced operation is switched off, and the output behaves in the same way as with pa-
rameter Behaviour at end of safety.
active: Forced operation is active again after bus voltage recovery or ETS reset. The switch
position of the output is determined by the parameterization of Contact position if forced opera-
tion.
With selection 2 bit object:
Options:
0 = inactive
2 = OFF
3 = ON
0 = inactive: Forced operation is switched off, and the output behaves in the same way as with
parameter Behaviour at end of safety.
2 = OFF: The communication object Forced Positioning is written with the value 2, and the out-
put is switched off.
3 = ON: The communication object Forced Positioning is written with the value 3, and the out-
put is switched on.
calculate present contact position
ON
OFF
unchanged