Threshold 1 upper limit
in W [0...4,600]
Options:
0...100...4,600
This is the upper hysteresis limit of threshold value 1. If the upper threshold is exceeded, there is a
reaction.
Threshold 1 warning
Options:
do not send
send 0 when exceeding
send 1 when exceeding
send 0 when falling below
send 1 when falling below
exceeding 0, falling below 1
exceeding 1, falling below 0
If threshold value 1 is exceeded or undershot, the parameterized value of the communication object
Threshold 1 warning (Active power) is sent.
Note
Exceeding the threshold means that the upper limit is exceeded, falling below the threshold
means that the lower limit is undershot.
Contact position when
falling below lower limit
Options:
no reaction
switch OFF until next switch operation
Contact position when
exceeding upper limit
Options:
no reaction
switch OFF until next switch operation
The output switches after threshold value 1 has been exceeded or has fallen below the limit, and
the parameterized Delay for switching has timed out.
Switching off is evaluated as a "normal" switch telegram, i.e., the output is not inhibited, and every
new switch telegram can switch the output again.
Enable threshold 2
Options:
no
yes
Parameterization of threshold value 2 is identical to threshold value 1.