ABB i-bus
KNX
Commissioning
Enable thresholds
Options:
yes: The parameters and communication objects for threshold 1 for monitoring the Active power total
are enabled. The following parameters appear:
no
yes
Overwrite thresholds with download
or ETS reset
Options:
no
yes
yes: The threshold values can be modified via the bus. With this setting, after a download or
ETS reset, the values changed on the bus are again overwritten with the parameterized values.
This setting applies for threshold value 1 and threshold value 2.
Threshold 1 lower limit
in W [0...13,800]
Options:
0...90...13,800
This is the lower hysteresis limit of threshold value 1. If the lower threshold is undershot, there is a
reaction.
Threshold 1 upper limit
in W [0...13,800]
Options:
0...100...13,800
This is the upper hysteresis limit of threshold value 1. If the upper threshold is exceeded, there is a
reaction.
Threshold 1 warning
Options:
do not send
send 0 when exceeding
send 1 when exceeding
send 0 when falling below
send 1 when falling below
exceeding 0, falling below 1
exceeding 1, falling below 0
If threshold value 1 is exceeded or undershot, the parameterized value of the communication object
Threshold 1 warning (Active power total) is sent.
Note
Exceeding the threshold means that the upper limit is exceeded, falling below the threshold
means that the lower limit is undershot.
Enable threshold 2
Options:
no
yes
Parameterization of threshold value 2 is identical to threshold value 1.