The following parameter appears with the selection Staircase lighting:
Staircase lighting duration
in s [0...65,535]
Options:
0...300...65,535
The staircase lighting time defines how long the contact is closed and how long the light remains on
after an ON telegram. The input is made in seconds. The staircase lighting time may extend de-
pending on the value set in the parameter Warning before end of staircase lighting.
Extending staircase lighting by
multiple operation ("pumping up")
Options:
no (not retriggerable)
yes (retriggerable)
up to max. 2x staircase lighting time
up to max. 3x staircase lighting time
up to max. 4x staircase lighting time
up to max. 5x staircase lighting time
If a further ON telegram is received during the staircase lighting time sequence, the remaining stair-
case lighting time can be extended by a further period. This is possible by repeated operation of the
push button ("pumping up") until the maximum programmed number of retriggering operations is
reached. The maximum time can be set to 1, 2, 3, 4 or 5-fold time of the staircase lighting time.
The staircase lighting time is extended by "pumping up" to the maximum time. If some of the time
has already timed out, the staircase lighting time can again be extended to the maximum time by
"pumping up". The parameterized maximum time may not however be exceeded.
no: The receipt of a further ON telegram is ignored. The staircase lighting time continues with-
out modification to completion.
yes (retriggerable): The staircase light time is reset each time by a renewed ON telegram and
starts to count again each time. This process can be repeated as often as desired using this
selection.
up to max. 2/3/4/5 x staircase lighting time: The staircase lighting time is extended by the
2/3/4/5-fold staircase lighting time with a renewed ON telegram.
Staircase lighting can be switched
Options:
ON with 1 and OFF with 0
ON with 1 no action with 0
ON with 0 or 1, switch OFF not possible
This parameter defines the telegram value used for switching the staircase lighting on and off
prematurely.
ON with 0 or 1, switch OFF not possible: The function Staircase lighting is switched on inde-
pendently of the value of the incoming telegram. Premature switch off is not possible.
Note
After enabling the function Time via the communication object Disable function time, the contact
position of the enabled output remains unchanged. Function Time is only triggered after the next
switching telegram. This means however, should the option ON with 1 no action 0 be parameter-
ized, the output is switched on simultaneously with enable. Switch off via the bus is thus not
possible. Only after, e.g. the function Staircase lighting is started, does the output switch off,
after the staircase lighting time has elapsed.