Commissioning
yes, object writable: The communication object Receive load limit is enabled. The parameterized load
limit can be modified via the bus. The following parameters appear:
Note
The following parameters determine, which of the up to 10 values are included for the calculation of the
Send sum power values. The power values of the master can be used (outputs A, B, C and/or the total
power) or the power values are received externally from a communication object, generally the active
power total from other Energy Actuators. The power values 1...4 may receive their value internally or
externally; power values 5...10 may only receive their value externally.
The sum of these power values is compared to the parameterized load limit for load control purposes.
If negative power values are received (power feed), they are not considered for load control.
Load limit 1 in W [0...200,000]
Load limit 2 in W [0...200,000]
Load limit 3 in W [0...200,000]
Load limit 4 in W [0...200,000]
Options
0...5000...200,000
Active load limit after download
or ETS reset
Options:
Load limit 1...4
The load limit parameterized here is active after a download or ETS reset.
Load limit in W [0...200,000]
Options:
0...5000...200,000
Overwrite load limit with download
or ETS reset
Options:
no
yes
yes: The load limit can be modified via the bus. With this selection, the parameterized value is
accepted again after a download or ETS reset.
SE/S 3.16.1 | 2CDC 505 084 D0203 47