ABB i-bus
KNX
Commissioning
No.
67
This communication object is enabled if in parameter window
been selected with the option yes.
Using this 8 bit communication object, a scene telegram can be received using a coded telegram. The telegram contains the
number of the respective scene as well as the information if the scene is to be called, or if the current switch state is to be
assigned to the scene.
Telegram format (1 byte):
For further information see:
68
This communication object is enabled if in parameter window
been selected with the option yes.
Using this communication object, the output of the first of two logic objects can be assigned. The logical connection is defined
in the parameter window A: Logic.
Initially the switch object is then logically linked with the communication object Logical. connection 1. The result is then linked
with the communication object Logical connection 2.
For further information see:
69
See communication object 68.
110 2CDC 505 084 D0203 | SE/S 3.16.1
Function
8 bit scene
MXSSSSSS
(MSB) (LSB)
M:
0 – scene is called
1 – scene is stored (if allowed)
X:
not used
S:
Number of the scene (1...64: 00000000 ... 00111111)
KNX 1 byte telegram value
Decimal
00
01
02
...
63
128
129
130
...
191
Code table scene (8
Logical connection 1
Function
Logic, page 132
Logical connection 2
Object name
A: Scene
A:
Function, page 55, the parameter Enable function scene has
Meaning
Hexadecimal
00h
Recall scene 1
01h
Recall scene 2
02h
Recall scene 3
...
...
3Fh
Recall scene 64
80h
Store scene 1
81h
Store scene 2
82h
Store scene 3
...
...
AFh
Store scene 64
bit), page 144
A: Logic
A:
Function, page 55, the parameter Enable function logic has
A: Logic
Data type
Flags
1 byte
C, W
DPT 18.001
1 bit
C, W
DPT 1.002
1 bit
C, W
DPT 1.002