Parameter window Function

In the parameter window Function, the functions and the corresponding communication objects for the en-
tire device are enabled.
Monitor "Active power total"
Options:
yes: The parameter window Active power total and the communication object Active power (Active
power total) are enabled.
Monitor "Frequency"
Options:
yes: The parameter window Frequency and the communication object Frequency are enabled.
Device is load control master
Options:
yes: The parameter window Load control master as well as the respective communication objects are
enabled.
Enable communication object
"Receive load shedding stage"
Options:
yes: The communication object Receive load shedding stage is enabled. This communication object is
required, provided that at least one of the outputs is parameterized with Load control slave and the
load shedding stage is received externally from a master or a visualization system. The load shedding
stage is received once per device and applies internally for all the outputs parameterized as a slave.
Necessary if at least 1 output is
load control slave
<−−− NOTE
no
yes
no
yes
no
yes
no
yes
SE/S 3.16.1 | 2CDC 505 084 D0203 35