Commissioning
3.3.8.2

Communication objects A: Intermediate meter

No.
75
This communication object is enabled if in parameter window
has been selected with the option yes.
The Intermediate meter is derived from the Meter total. It is controlled via communication objects no. 76...79.
76
This communication object is enabled if in parameter window
has been selected with the option yes. The value of the communication object is sent when a telegram is received on the
communication object Request status values.
This communication object indicates whether the counter is currently started or stopped and whether the meter reading could
be erroneous. This can be the case, for example, during a start or stop event if bus voltage is not available and this event is
thus not recorded.
Telegram value:
Bit 0:
Bit 1:
Bit 2...7:
77
This communication object is enabled if in parameter window
activated by has been selected with the option 1 bit object.
The intermediate meter starts if a telegram with the value 1 is received via this communication object. You can parameterize
whether the intermediate readings are reset and/or sent.
77
This communication object is enabled if in parameter window
activated by has been selected with the option Time.
The parameterized start time can be modified using this communication object.
If the parameterized start time is received via the communication object Receive time (no. 8), the intermediate meter starts.
You can parameterize whether the intermediate readings are reset and/or sent.
78
This communication object is enabled if in parameter window
activated by has been selected with the option 1 bit object.
The intermediate meter is sent if a telegram with the value 1 is received via this communication object. You can parameterize
whether the intermediate meter stops or continues to count, or whether the output switches at stop when trigger 2 is received.
112 2CDC 505 084 D0203 | SE/S 3.16.1
Function
Meter reading
Status
1 = meter reading is started
0 = meter reading is stopped
1 = since the last reset of the intermediate meter a bus voltage failure or download has occurred. The
meter reading may not be correct.
0 = since the last reset of the intermediate meter no bus voltage failure or download has occurred.
Not assigned, 0.
Receive trigger 1
Trigger 1 change time
Receive trigger 2
Object name
A: Intermediate meter
A:
Function, page 55, the parameter Enable function metering
A: Intermediate meter
A:
Function, page 55, the parameter Enable function metering
A: Intermediate meter
A: Metering
(Wh), page 73, the parameter Trigger 1 (Start) is
A: Intermediate meter
A: Metering
(Wh), page 73, the parameter Trigger 1 (Start) is
A: Intermediate meter
A: Metering
(Wh), page 73, the parameter Trigger 2 (Start) is
Data type
Flags
4 byte
C, R, T
DPT 13.010
1 byte
C, R, T
NON DPT
1 bit
C, W
DPT 1.017
3 byte
C, R, W, T
DPT 10.001
1 bit
C, W
DPT 1.017