ABB i-bus KNX Product Manual page 67

Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Start-up
Limit step commands to
number of slat adjustments
Options:
This parameter specifies whether step commands are limited to a set number of slat adjustments or
whether than can always be executed.
Yes: Only that number of slat adjustments or step commands can be executed as were set in the
parameter Number of slat adjustments [1...60].
No: The slat adjustments and step commands of the blind/shutter can be controlled without restriction.
Total turning of slats after move DOWN
Options:
This parameter can be used to release slats which have become stuck or got caught during movement.
This functions is primarily used for slats in the pane cavity of a window.
Yes: After a DOWN movement, the slats are turned fully once (CLOSED – OPEN – CLOSED). If a
DOWN movement is interrupted by a STOP command, no turn is executed.
No: No action occurs after a DOWN movement.
Position of slat after arriving on
lower end position (100% = disabled)
Options:
This parameter specifies the slat position the blind/shutter is to assume on reaching the lower end position.
When blind/shutter has reached to the lower end position, the slats are normally closed.
100 %: The slats are CLOSED.
...%: The slats are moved to the appropriate intermediate position.
0 %: The slats are completely OPEN.
Yes
No
Yes
No
100 %
...
0 %
JRA/S | 2CDC 506 051 D0204 65