Parameter Window A: Drive - ABB i-bus KNX Product Manual

Blind/roller shutter actuators jra/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Start-up
3.2.5.2

Parameter window A: Drive

Detect travel times (Up/Down)
Options:
Yes - via detection of end positions: The parameters for setting and triggering the automatic travel
detection appear.
Note
Automatic travel detection is only available for devices of type JRA/S x.y.5.1.
In the case of all other types (JRA/S x.y.2.1 and JRA/S x.y.1.1), the parameters for travel time UP or
DOWN are shown in the ETS.
In the case of devices of type JRA/S 4.230.5.1 and JRA/S 8.230.5.1, automatic travel detection via
detection of end positions must always be parameterized in pairs for both outputs of a root (e.g. A+B,
C+D, etc.). The connected drives should be of the same type or have the same current consumption.
Mixed parameterization is not permitted and can lead to errors in travel time detection. Example:
Parameter
Detect travel times
(up/down)
Detect travel times
(up/down)
Note
When electronic drives with a permanent power supply are used, automatic travel detection is not
possible, as the current consumption does not take place via the UP or DOWN contact. When electronic
drives of this type are used, the travel times must be determined and input manually.
58 2CDC 506 051 D0204 | JRA/S
Yes - via detection of end positions
No - set travel times
Output A
Parameter option
Yes – via detection of end
positions
No – set travel times
Output B
Parameter option
Yes – via detection of end
positions
Yes – via detection of end
positions
Note
OK
Not permitted