Installation Site Requirements; Commercial Power; Environmental Requirements; Equipment Room Recommendations - Toshiba Perfecptione Installation And Maintenance Manual

Digital pbx
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
SECTION 200-255-203
FEBRUARY 1992
CHAPTER 3
INSTALLATION SITE REQUIREMENTS
1. COMMERCIAL POWER
1 .OO The system requires a power source of 100 m
120 VAC, 50/60 Hz. The AC outlet must be dedi-
catedto system use, grounded and fused. To avoid
accidental power turn-off, it is recommended that
an ON/OFF wall switch not be used on this dedi-
cated AC circuit.
1 .Ol If reserve power is to be installed, the battery
pack requires a well-ventilated location adjacent to
the equipment cabinet.
2. ENVIRONMENTAL REQUIREMENTS
2.00 Humidity at the equipment cabinet should be
within 20 - 80% (non-condensing), and the tem-
perature should be relatively constant within 32 w
104°F (0 w 40°C). Exposure to dust and airborne
chemicals should be avoided.
3. EQUIPMENT ROOM RECOMMENDATIONS
3.00 The minimum floor and maintenance space
required for installation of each of the two equip-
ment cabinets is shown in Figures 3-l and 3-2.
I
I
I
REAR WALL
t
I
4
6" AIR SPACE' THREE SIDES i
I
c
I
I
I
I
1
t
1
Y
17 314"
I
I
I
I
I
I
lb
I I
1 1
1 2"
I I
I I
I I
I I
I I
TOP VIEW
TOP VIEW
I I
I I
I I
I I
8 8
NCEC202-M UNIT
NCEC202-M UNIT
I I
I I
I I
I I
I I
I
I
I
I
c
w
I
I
I
I
I
I
I
4
I
I
I
I
FRONT WORK SPACE APPROXIMATELY 36"
FRONT WORK SPACE APPROXIMATELY 36"
; ;
I I
+ +
I I
I I
I I
I I
I I
I I
FIGURE 3-I-PERCEPTION,
MINIMUM FLOOR SPACE
l
Stand-alone DDIU-MA/PDIU-DS - 3, 280 cable
feet (1,000 M), 24 AWG
l
Attendant Console - 1,000 cable feet (305 M),
24 AWG
3.01 The following requirements must be consid-
l
Electronic DSS - 500 cable feet, 24 AWG
I
I
REAR WALL t
I
I
6" AIR SPACE THREE
f
A
22"
I
1 2"
TOP VIEW
LCEC-M UNIT
I
I
FRONT WORK SPACE APPROXIMATELY 36"
I
I
f
FIGURE 3-P-PERCEPTION,
MINIMUM FLOOR SPACE
ered when selecting a location for the equipment
cabinet:
The location MUST BE:
l
Dry and clean.
l
Well ventilated.
l
Well lit.
l
Easily accessible.
The location MUST NOT BE:
l
Subject to extreme heat or cold.
l
Subject to corrosive fumes.
l
Next to a reproducing or copying ma-
chine.
4. CABLING CONSIDERATIONS
4.00 The equipment cabinet must be located close
to the facility Main Distribution Frame (MDF). Maxi-
mum house cable run distances for station and
peripheral equipment must also be considered
when choosing the location of the equipment cabi-
net. The limit for each type of equipment is:
l
Electronic/Digital Telephone - 1,000 cable feet
(305 M), 24 AWG
l
Standard Telephone - 500-ohms (including tele-
phone)
3-1